top of page

HE3DA 1500

Product Specifications

 

BATTERY PARAMETERS 1500 kWh: HE3DA BTS 1,3 kWh battery

Articles: ................................................................................................. 1176

Storage tank: .................................................................................................. 6

Maximum stored energy: ............................................... 1528.8 kWh

Rated energy: ................................................................ 1411.2 kWh

Energy at 80% recommended DOD: ............................... 1234.8 kWh

DV 20' dimensions (length (front) x depth x height):

..................................................................................... 2.44 x 6.06 x 2.59 m

Weight: ............................................................................... <24000 kg

Recommended continuous charging: ............................................... 0.14 C

Recommended continuous discharge: ............................................... 0.35 C

Operating temperature: ........................................................... -30 °C ∼ +50 °C

Intrusion protection: .................................................................. IP 54

Battery life (in accordance with the recommended operating values below) ............................................................... >5000

Battery technology: ......................................................... li-ion HE3DA

 

BIDIRECTIONAL INVERTER

PARAMETERS: BFI2z 500T

 

Rated voltage: ............................................ 3x400 V AC (+10/-15)%

Rated current:......................................................................... 3x795 A

Rated power: ..................................................... 400/500 kW/kVA

Maximum supply voltage: .................................................... 825 V DC

Minimum supply voltage: .................................................... 550 V DC

Output voltage: .................................................................. 0.4 kV (±2%)

Voltage Frequency: ............................................................ 50 Hz (±0.1%)

Output power: .......................................................................... 500 kVA

Conversion current: ......................................................................... 3x723 A

Overload: ............................................................................ 1.1-1.25In 1 min

                                                                                                           1,25-1,5In 30 s

                                                                                                               >1,5In 1 sec

Efficiency: ......................................................................................... >94%

Inverter short-circuit current: ................................. 2 x In (up to 5 x In) A

bottom of page